Transformer Partial Discharge: Causes, Testing, Limits

Classification:

Industry News

Release time:

2026-10-19


Insulation & Testing

Partial Discharge in Transformers: Causes, Testing and Acceptable Limits

What Partial Discharge Is and Why It Matters

Each discharge event is very small, but it repeats thousands of times per second. It erodes the insulation at its source, and the damage can grow until a full breakdown occurs.

  • It is progressive. A transformer with active PD usually keeps operating normally in the early stages.
  • It can't be seen from the load side. Temperature and current look normal, so it needs a dedicated test.
  • Dry-type units have no liquid buffer. In a liquid-filled transformer, oil can partly cool and quench small discharges. A dry-type transformer relies on solid insulation and air.
Transformer winding cross-section Conductor Conductor Gas void Solid insulation Discharge occurs inside the void, not bridging the two conductors Core LV winding HV winding Cast resin insulation
Figure 1 · Partial discharge concept cross-section. Partial discharge occurs inside a gas void in the insulation. The discharge channel only spans the void and does not bridge the full insulation thickness, so it does not cause immediate breakdown — but it does erode the insulation over time.

Where PD Starts

PD types and typical initiation sites
Type Typical cause Where
Internal (void) discharge Gas voids or cracks in solid insulation Cast resin coils, bushings
Corona Sharp edges or high electric field at a point Terminals, leads, core edges
Surface discharge and tracking Moisture, dust or contamination on a surface Coil surfaces, supports
Gas bubbles and floating parts Gas in oil, loose metal pieces Oil-immersed units

PD tends to develop in predictable places, such as coil ends, the high-voltage terminals, and where cables are connected.

Four types of partial discharge and common initiation sites Internal (void) discharge Internal void discharge Gas voids or cracks inside solid insulation Common in cast resin coils and bushings Corona Corona discharge Sharp edges or localized high-field points Common at terminals, leads and core edges Surface discharge & tracking Surface discharge & tracking Moisture, dust or contamination on surfaces Common on coil surfaces and supports Gas bubbles & floating parts Gas bubbles & floating parts Gas in oil or loose metal particles Common in oil-immersed units
Figure 2 · Types of partial discharge and initiation sites. Different discharge mechanisms start in different places, usually at winding ends, HV terminals, cable connections and support insulators. Identifying the discharge type helps determine whether the cause is design, manufacturing or operating environment.

How PD Is Measured

  • Unit: apparent charge in pC, measured with a calibrated circuit as described in IEC 60270.
  • Factory test: for dry-type transformers, the PD test is normally combined with the induced voltage test. According to test-equipment documentation, it is required for dry-type units above 3.6 kV under IEC 60076-11 and IEEE C57.12.01.
  • Typical limits: commonly cited limits are about 10 pC for solid cast windings and about 50 pC for resin-encapsulated windings. The exact value comes from the standard and your specification.
  • Liquid-filled units: PD is measured during the induced voltage test, with the acceptance level agreed in the specification. For distribution transformers it is often requested as a special test.
IEC 60270 partial discharge measurement principle (simplified) Calibration pulse generator Injects known charge via Ccal AC power supply Test transformer (induced voltage test) Ck Coupling capacitor Zm Measuring impedance PD measuring instrument IEC 60270 HV terminal A calibration pulse injects a known charge to calibrate the pC reading of the whole measuring circuit
Figure 3 · IEC 60270 partial discharge measurement principle (simplified). During the induced voltage test, PD pulses from the test transformer pass through the coupling capacitor Ck into the measuring impedance Zm and are recorded as apparent charge in pC by the PD instrument. A calibration pulse generator injects a known charge for calibration before the test, and the background noise level is recorded.

IEC 60076-11 covers dry-type power transformers up to a highest voltage for equipment of 72.5 kV. Always confirm the edition and limits in your contract.

Typical partial discharge limits (reference) (Typical values; actual limits per applicable standard edition and contract) 0 10 20 30 40 50 60 pC Cast resin winding ~10 pC Resin-encapsulated winding ~50 pC Oil-immersed transformers: measured during the induced voltage test; acceptance limits per standard and contract; often a special test for distribution units
Figure 4 · Typical partial discharge limit comparison. For dry-type transformers, a commonly cited target for cast resin windings is around 10 pC, while resin-encapsulated windings are often around 50 pC. Absolute limits must follow the applicable standard edition and the technical agreement in the contract; different voltage classes and designs may use different values.

Reading the Numbers: A Worked Example

PD trend across the transformer lifecycle (illustrative)
Stage PD level (illustrative)
Factory test 8 pC
Commissioning on site 11 pC
12 months later 29 pC

Every value is still low in absolute terms, but the level has more than doubled in a year. The right response is to re-test within a few months, inspect for dust and moisture, check cable terminations, and compare with the factory baseline. A stable reading close to the factory value is generally unremarkable, while a steady climb is the signal.

Partial discharge trend example: 8 pC → 11 pC → 29 pC (Illustrative data to show how trend assessment works) 0 10 20 30 pC 8 pC 11 pC 29 pC Factory test Commissioning on site 12 months later Trend matters more than a single reading
Figure 5 · Partial discharge trend case. All three values are low in absolute terms, but the level has more than tripled within a year — a clear upward trend. The right response is to re-test within a few months, inspect for dust, moisture and cable terminations, and compare with the factory baseline. A stable reading close to the factory value is generally unremarkable; a steady climb is the signal.
Site conditions can change the result. A transformer can pass the factory test at 10 pC and read much higher in service simply because of how cables are routed or terminated. Test in the final configuration.

How to Reduce PD

In design and manufacturing

  • Vacuum casting and curing to avoid voids in cast resin coils.
  • Rounded edges and field grading to limit corona.
  • Clean, controlled production and routine PD testing of every unit.

On site and in service

  • Keep the room dry, ventilated and clean. Moisture and airborne pollution promote surface discharge.
  • Install cable terminations carefully with proper stress control and clearances.
  • Add space heaters or humidity control in damp locations.
  • Schedule inspections as in our dry-type transformer maintenance checklist.

For critical sites, online PD monitoring (for example, high-frequency or acoustic sensors) can trend activity between outages.

PD Is One Test Among Several

PD shows the condition of the insulation, but it works best alongside other checks:

What to Put in Your RFQ

  1. PD test required for every dry-type transformer, with the standard (for example IEC 60076-11) and the acceptance limit in pC.
  2. Test voltage and measuring method per IEC 60270, with the background noise level reported.
  3. Results per phase in the test certificate, not only a pass/fail statement.
  4. Witness test option for large or critical orders.
  5. Final-configuration retest on site if cable runs or enclosures are unusual.
  6. For oil-immersed units, specify whether the induced voltage test with PD measurement is required as a special test.

Our procurement and RFQ guides list the other parameters to include.

Matching Products to PD Requirements

Product options by application
Need Aisite option
Indoor dry-type distribution 10KV Dry type transformer (Yyn0, Dyn11) and 20KV Dry type transformer
Oil-immersed distribution 10KV Oil Immersed Transformers and 20KV Oil Immersed Transformer (11–33 kV, 50 kVA–20 MVA)
Higher voltage 35KV Oil Immersed Transformer
Packaged installation Compact substation and HV LV Switchgear
Specific PD limit, test voltage or witness test Customized Transformer

Pre-Order and Commissioning Checklist

  • PD acceptance limit (pC) and standard written into the specification
  • Per-phase PD results required in the test certificate
  • Factory baseline kept for later comparison
  • Site tested in the final configuration
  • Room humidity, ventilation and cleanliness planned
  • Re-test interval and trend alarm level defined
  • Online monitoring considered for critical units

FAQ

What is an acceptable PD level in a transformer?

It depends on the standard and your specification. For cast resin dry-type transformers, around 10 pC is a commonly cited target. The trend over time is as important as the absolute value.

Does partial discharge mean the transformer will fail?

Not immediately. It is a progressive process, and the risk depends on the level, the location and how fast it grows.

Can PD be measured while the transformer is energized?

Yes. Online methods use special sensors. Offline tests, such as the factory induced test, give the most accurate baseline.

Do oil-immersed transformers need PD tests?

They are often measured during the induced voltage test, especially for higher voltages, and can be specified as a special test for distribution units.

Can Aisite quote to a specific PD limit?

Yes. Send your standard, limit and test requirements, and our engineers will review them through the Customized Transformer line.

Get a Project-Specific Recommendation

Send your voltage, kVA rating, installation conditions and test requirements, and our engineers will suggest a configuration.

Contact us Browse full product range

This guide is general engineering information. Acceptance limits and test methods must follow the applicable standard edition and your contract.

Technical sources IEC 60076-11:2018 scope (IEC/AFNOR catalog entry); Haefely test note on PD testing of dry-type transformers (IEC 60076-11 and IEEE C57.12.01); Rex Power Magnetics article on PD in dry-type transformers.